N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 14-10.13

Current through Register Vol. 46, No. 53, December 31, 2024
Section 14-10.13 - Setting of safety valves

One or more safety valves on every boiler shall be set at or below the maximum allowable working pressure. The remaining valves may be set within a range of three percent above the maximum allowable working pressure, but the range of setting of all of the valves on a boiler shall not exceed 10 percent of the highest pressure to which any valve is set.

N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 14-10.13