The safety valve capacity of each boiler shall be such that the safety valve or valves will discharge all the steam that can be generated by the boiler without allowing the pressure to rise more than six percent above the maximum allowable working pressure, or more than six percent above the highest pressure to which any valve is set.
N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 14-10.12