Table 1 | ||||
CAPACITY PER UNIT EGRESS WIDTH | ||||
Without automatic sprinkler a system | With automatic sprinkler system Number of | |||
Number of occupants | occupants | |||
Group | Stairways | Doors, Ramps and Corridors | Stairways | Doors, Ramps and Corridors |
A | 75 | 100 | 113 | 150 |
B | 60 | 100 | 90 | 150 |
E | 75 | 100 | 113 | 150 |
F | 60 | 100 | 90 | 150 |
H | - | - | 60 | 100 |
I-1 | 60 | 100 | 90 | 100 |
I-2 / | 22 | 30 | 35 | 45 |
I-4 | ||||
I-3 | 60 | 100 | 90 | 150 |
M | 60 | 100 | 90 | 150 |
R | 75 | 100 | 113 | 150 |
S | 60 | 100 | 90 | 150 |
Note: The occupant load may be equal to the total number of occupants for which exit capacity is provided as determined by Table 1 above. For Group A occupancies, the resulting total occupant load shall not exceed one occupant per five square feet of net floor area over the entire use.
Interpolation shall be allowed in determining capacity of egress width.
Unit of egress width = 22 inches
Table 2 | |||
Existing Interior Finish Requirements | |||
Group | Exit Enclosures | Exit Access Enclosures | Rooms or Spaces |
A, E, I, R-1 | I | II | III |
All Other Groups | I | II | No Minimum |
The classification of interior finishes referred to herein corresponds to flame spread ratings determined by ASTM E84 as follows: Class I flame spread, 0-25; Class II flame spread, 26-75; Class III flame spread, 76-200. In all cases, the smoke developed rating determined by ASTM E84 shall not exceed 450. | |||
See Group A-3 for amusement buildings. |
N.J. Admin. Code § 5:23-6.11
See: 31 N.J.R. 2428(a), 31 N.J.R. 4001(c).
In (b), rewrote the note at the end of Table 1.
Amended by R.2004 d.145, effective 4/5/2004.
See: 35 N.J.R. 5190(a), 36 N.J.R. 1758(a).
Deleted references to use preceding references to group throughout; in (c)1iii, substituted a reference to automatic sprinkler for a reference to fire suppression; in (d), substituted references to fire extinguishing system for references to fire suppression throughout.
Amended by R.2006 d.120, effective 4/3/2006.
See: 37 N.J.R. 3753(a), 38 N.J.R. 1567(a).
In (b)1, added Group I-4 to Table 1.
Amended by R.2007 d.51, effective 2/5/2007.
See: 38 N.J.R. 375(a), 39 N.J.R. 371(a).
In the introductory paragraph of (b)1, deleted "(Plan review--Building, Fire. Inspection--Building)" following "capacity"; and added new (b)1i.
Amended by R.2007 d.338, effective 11/5/2007.
See: 39 N.J.R. 280(a), 39 N.J.R. 4569(a).
Added (e).