N.J. Admin. Code § 5:23-6.11A

Current through Register Vol. 56, No. 21, November 4, 2024
Section 5:23-6.11A - Supplemental requirements in all Groups
(a) This section shall apply to all reconstruction projects.
(b) Vertical Opening Protection: For purposes of applying the supplemental requirement for vertical opening protection below, a low hazard occupancy is an occupancy having contents of such low combustibility that no self-propagating fire can occur therein. A moderate hazard occupancy is an occupancy having contents that are likely to burn with moderate rapidity or to give off a considerable volume of smoke. (Plan review--Building, Fire. Inspection-Building)
(c) Windowless Stories: Any windowless basement or story located below the seventh story which is created by the work being performed or any existing windowless basement or story below the seventh story in which the work area exceeds 50 percent of the gross enclosed floor area of the windowless story, shall comply with the requirements listed in 5:23-6.30. (Fire)
(d) Underground Structures: When the work area exceeds 50 percent of the gross enclosed floor area of an underground structure, the entire structure shall comply with Section 405 of the building subcode.

N.J. Admin. Code § 5:23-6.11A

Amended by R.2004 d.145, effective 4/5/2004.
See: 35 N.J.R. 5190(a), 36 N.J.R. 1758(a).
Amended by 53 N.J.R. 245(a), effective 2/16/2021