675 Ind. Admin. Code 14-4.4-92

Current through November 6, 2024
Section 675 IAC 14-4.4-92 - Table N1102.1.4; equivalent U-factors [a]

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 92.

Delete TABLE N1102.1.4 and substitute to read as follows:

TABLE N1102.1.4 EQUIVALENT U-FACTORSa

CLIMATE ZONE FENESTRATION U-FACTOR SKYLIGHT U-FACTOR CEILING U-FACTOR FRAME WALL U-FACTOR MASS WALL U-FACTORb FLOOR U-FACTOR BASEMENT WALL U-FACTOR CRAWL SPACE WALL U-FACTOR
4 0.35 0.60 0.030 0.082 0.141 0.047 0.059 0.065
5 0.35 0.60 0.030 0.067 0.082 0.033 0.059 0.065

a.Non-fenestration U-factors shall be obtained from measurement, calculation, or an approved source.
b. When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.10 in zone 4 and the same as the frame wall U-factor (0.057) in zone 5.

675 IAC 14-4.4-92

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-92; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA