Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7
Sec. 91.
Delete TABLE N1102.1.2 and substitute to read as follows:
TABLE N1102.1.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
CLIMATE ZONE | FENESTRATION U-FACTOR | SKYLIGHT U-FACTORb | CEILING R-VALUE | WOOD FRAME RVALUE | MASS WALL R-VALUEg | FLOOR RVALUE | BASEMENT WALL R-VALUEc | SLAB RVALUE AND DEPTHd | CRAWL SPACE RVALUE |
4 | 0.35 | 0.60 | 38 | 15 | 5/10 | 19 | 10/13 | 10; 2 feet | 10/13 |
5 | 0.35 | 0.60 | 38 | 20 or 13+5f | 13/17 | 30e | 10/13 | 10; 2 feet | 10/13 |
a. R-values are minimums. U-factors are maximums. Batts compressed into a framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value.b. The fenestration U-factor column excludes skylights.c. The first R-value applies to continuous insulation, the second to framing cavity insulation; either insulation meets the requirement.d. Minimum of R-5 shall be provided under the full slab area of heated slabs in addition to the required slab edge insulation R-value for slab as indicated in the table. The slab edge insulation for heated slabs shall not be required to extend below the slab.e. R-30 or insulation sufficient to fill the framing cavity, R-19 minimum.f."13+5" means R-13 cavity insulation with an additional R-5 insulated sheathing applied to the exterior of the wall. If structural sheathing covers 25% or less of the exterior, R-5 sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25% of exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.g. The second R-value applies when more than half the insulation is on the interior.Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-91; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA