Each method of release detection for tanks used to meet the requirements of sections 11-280.1-40 to 11-280.1-42 must be conducted in accordance with the following:
Nominal lank capacity | Minimum duration of test | Weekly standard (one test) | Monthly standard (four test average) |
550 gallons or less ............................................................ | 36 hours........ | 10 gallons........ | 5 gallons |
551-1,000 gallons (when tank diameter is 64 inches)....................... | 44 hours........ | 9 gallons......... | 4 gallons |
551-1,000 gallons (when tank diameter is 48 inches).................. | 56 hours............. | 12 gallons........... | 6 gallons |
551-1,000 gallons (also requires periodic tank tightness testing) "..... | 36 hours.......... | 13 gallons.......... | 7 gallons |
1,001-2,000 gallons (also requ res periodic tank tightness testing).. | 36 hours............ | 26 gallons........ | 13 gallons |
Haw. Code R. § 11-280.1-43