Each method of release detection for piping used to meet the requirements of sections 11-280.1-40 to 11-280.1-42 must be conducted in accordance with the following:
MAXIMUM LEAK DETECTION RATE PER TEST SECTION VOLUME
Test section volume (gallons) | Semiannual test-leak detection rate not to exceed (gallons per hour) | Annual test-leak detection rate not to exceed (gallons pel hour) |
<50,000....... | 1.0 | 0.5 |
>=50,000 to <75,000......... | 1.5 | 0.75 |
>=75 000 to <100,000......... | 2.0 | 1.0 |
>=100,000...................... | 3.0 | 1.5 |
PHASE IN FOR PIPING SEGMENTS >=100,000 GALLONS IN VOLUME
First test................ | Not later than three years after the effective date of these rules (may use up to 6.0 gph leak rate). |
Second test........... | Between three and six years after the effective date of these rules (may use up to 6.0 gph leak rate). |
Third test............... | Between six and seven years after the effective date of these rules (must use 3.0 gph for leak rate). |
Subsequent tests.. | Not later than seven years after the effective date of these rules, begin using semiannual or annual line testing according to the Maximum Leak Detection Rate Per Test Section Volume table above. |
Haw. Code R. § 11-280.1-44