TABLE 322.32
STEEL-FRAME CEILING, WALL AND FLOOR INSULATION R-VALUES
Wood Frame R-Value Requirement | Cold-Formed Steel Equivalent R-Valuea |
Steel Truss Ceilingsb | |
R-30 | R-38 or R-30 + 3 or R-26 + 5 |
R-38 | R-49 or R-38 + 3 |
R-49 | R-38 + 5 |
Steel Joist Ceilingsb | |
R-30 | R-38 in 2X4 or 2X6 or 2X8 R-49 in any framing |
R-38 | R-49 in 2X4 or 2X6 or 2X8 or 2X10 |
Steel Framed Wall | |
R-13 | R-13 + 5 or R-15 + 4 or R-21 + 3 |
R-19 | R-13 + 9 or R-19 + 8 or R-25 + 7 |
R-21 | R-13 + 10 or R-19 + 9 or R-25 + 8 |
Steel Joist Floor | |
R-13 | R-19 in 2X6 R-19 + 6 in 2X8 or 2X10 |
R-19 | R-19 + 6 in 2X6 R-19 + 12 in 2X8 or 2X10 |
a Cavity insulation R-value is listed first, followed by continuous insulation R-value.
b Insulation exceeding the height of the framing shall cover the framing.
Wis. Admin. Code Department of Safety and Professional Services SPS 322.32