Note: UA is equal to the product of the U-factor times the assembly area.
Note: REScheck is an acceptable software program for determining compliance with this section.
Note: The IECC 2009 version of REScheck meets the thermal envelope requirements of this code.
TABLE 322.31-1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
Zone | Fenestration U-Factor | Skylight U-Factor | Ceiling R-Value | Wood Frame Wall R-Value | Mass Wall R-Valuei | Floor R-Value | Basement Wall R-Valueb | Crawl Space Wall R-Valueb | Heated Slab R-Valuec | Unheated Slab R-Valued |
1 | 0.35 | 0.60 | 49e | 20f or 13+5g | 15/19 | 30h | 15/19 | 10/13 | 10/15 | 10 |
2 | 0.35 | 0.60 | 49e | 21f | 19/21 | 38h | 15/19 | 10/13 | 10/15 | 10 |
a R-values are minimums. U-factors are maximums.
b "15/19" means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.
c The first R-value applies under the entire slab, regardless of depth below grade. The second R-value applies to the slab edge where the bottom of the slab is less than 12 inches below adjacent grade. Slab edge insulation shall extend downward from the top of the slab for a minimum of 48 inches or downward to at least the bottom of the slab and then horizontally to the interior or exterior for a minimum total distance of 48 inches. Also, see s. SPS 321.16 for protection against frost for slabs with supports less that 4 feet below grade.
d The R-value applies to any slab, the bottom of which is less than 12 inches below adjacent grade. Also, see s. SPS 321.16 for protection against frost for slabs with supports less than 4 feet below grade.
e See s. SPS 322.32(1) for application and permitted reduced R-value.
f R-20 and R-21 may be compressed into a 2X6 cavity.
g "13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25% or less of the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25% of the exterior, structural sheathing shall be covered with insulated sheathing of at least R-2.
h Or insulation sufficient to fill the framing cavity with a minimum of R-19.
i The second R-value applies when more than half of the insulation is on the interior of the mass wall.
TABLE 322.31-2
EQUIVALENT U-FACTORS
Zone | Fenestration U-Factor | Skylight U-Factor | Ceiling U-Factor | Wood Frame Wall U-Factor | Mass Wall U-Factor | Floor U-Factor | Basement Wall U-Factor | Crawl Space U-Factor | Unheated Slab U-Factor |
1 | 0.35 | 0.60 | 0.026 | 0.057 | 0.060a | 0.033 | 0.050 | 0.065 | 10 |
2 | 0.35 | 0.60 | 0.026 | 0.057 | 0.057a | 0.028 | 0.050 | 0.065 | 10 |
a When more than half the insulation is on the interior, the mass wall U-factors shall be the same as the frame wall U-factor.
TABLE 322.31-3
WARM AIR FURNACES AND BOILERS, MINIMUM EFFICIENCY REQUIREMENTS
Equipment Type | Minimum Efficiency | Test Procedure |
Natural gas and propane furnace | 90% AFUE | DOE 10 CFR Part 430 or ANSI Z21.47 |
Natural gas and propane hot water boilers | 90% AFUE | DOE 10 CFR Part 430 |
Oil-fired furnaces | 83% AFUE | DOE 10 CFR Part 430 or UL 727 |
Oil-fired hot water boilers | 84% AFUE | DOE 10 CFR Part 430 |
TABLE 322.31-4
COMPONENT DWELLING THERMAL ENVELOPE REQUIREMENTS FOR DWELLINGS USING LOWER EFFICIENCY APPLIANCESa
Fenestration U-Factor | Skylight U-Factor | Ceiling R-Value | Wood Frame Wall R-Value | Mass Wall R-Value | Floor R-Value | Basement or Crawl Space Wall R-Valueb | Heated Slab R-Valuec | Unheated Slab R-Valued |
0.30 | 0.60 | 49e | 21f or 19+5g | 19 | 30h | 15/19 | 10/20 | 15 |
Equivalent U-Factors | ||||||||
0.30 | 0.60 | 0.026 | 0.057 | 0.057 | 0.033 | 0.045 | 0.033 | 0.047 |
a R-values are minimums. U-factors are maximums.
b The first R-value applies to continuous insulation. The second R-value applies to framing cavity insulation.
c The first R-value applies under the entire slab, regardless of depth below grade. The second R-value applies to the slab edge. Slab edge insulation shall extend downward from the top of the slab for a minimum of 48 inches or downward to at least the bottom of the slab and then horizontally to the interior or exterior for a minimum total distance of 48 inches.
d The R-value applies to the slab perimeter insulation, where the bottom of the slab is less than 12 inches below adjacent grade. Slab edge insulation shall extend downward from the top of the slab for a minimum of 48 inches or downward to at least the bottom of the slab and then horizontally to the interior or exterior for a minimum total distance of 48 inches. Also, see s. SPS 321.16 for protection against frost for slabs with supports less than 4 feet below grade.
e See s. SPS 322.32(1) for application and permitted reduced R-value.
f R-21 may be compressed into a 2X6 cavity.
g "19+5" means R-19 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25% or less of the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25% of the exterior, structural sheathing shall be covered with insulated sheathing of at least R-2.
h Or insulation sufficient to fill the framing cavity with a minimum of R-19.
Wis. Admin. Code Department of Safety and Professional Services SPS 322.31