Wash. Admin. Code § 51-11R-40551

Current through Register Vol. 24-23, December 1, 2024
Section 51-11R-40551 - Table R405.4.2(1)-Specifications for the standard reference and proposed designs

TABLE R405.4.2(1)

SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS

BUILDING COMPONENT

STANDARD REFERENCE DESIGN

PROPOSED DESIGN

Above-grade walls

Type: Mass wall if proposed wall is mass; otherwise wood frame.

Gross area: Same as proposed

U-factor: From Table R402.1.2

Solar absorptance = 0.75

Emittance = 0.90

As proposed

As proposed

As proposed

As proposed

As proposed

Below-grade walls

Type: Same as proposed

Gross area: Same as proposed

U-factor: From Table R402.1.2, with insulation layer on interior side of walls.

As proposed

As proposed

As proposed

Above-grade floors

Type: Wood frame

Gross area: Same as proposed

U-factor: From Table R402.1.2

As proposed

As proposed

As proposed

Ceilings

Type: Wood frame

Gross area: Same as proposed

U-factor: From Table R402.1.2

As proposed

As proposed

As proposed

Roofs

Type: Composition shingle on wood sheathing Gross area: Same as proposed Solar absorptance = 0.75 Emittance = 0.90

As proposed

As proposed

As proposed

As proposed

Attics

Type: Vented with aperture = 1 ft2 per 300 ft2 ceiling area

As proposed

Foundations

Type: Same as proposed foundation wall area above and below-grade

Soil characteristics: Same as proposed.

As proposed

As proposed

Opaque doors

Area: 40 ft2

Orientation: North

U-factor: Same as fenestration from Table R402.1.2.

As proposed

As proposed

As proposed

Vertical fenestration other than opaque doorsa

Total areah =

(a) The proposed glazing area; where proposed glazing area is less than 15% of the conditioned floor area.

(b) 15% of the conditioned floor area; where the proposed glazing area is 15% or more of the conditioned floor area.

As proposed

Orientation: Equally distributed to four cardinal compass orientations

(N, E, S & W).

As proposed

U-factor: From Table R402.1.2

As proposed

SHGC: From Table R402.1.1 except that for climates with no requirement (NR) SHGC = 0.40 shall be used.

As proposed

Interior shade fraction: 0.92 - (0.21 × SHGC for the standard reference design)

External shading: None

0.92 - (0.21 × SHGC as proposed)

As proposed

Skylights

None

As proposed

Air exchange rate

Air leakage rate of 4 air changes per hour at a pressure of 0.2

inches w.g. (50 Pa). The mechanical ventilation rate shall be in addition to the air leakage rate and the same as in the proposed design, but no greater than 0.01 × CFA +7.5 × (Nbr + 1)

where:

CFA = conditioned floor area

Nbr = number of bedrooms

- The mechanical ventilation system type shall be the same as in the proposed design. Energy recovery shall not be assumed for mechanical ventilation.

As proposeda. The mechanical ventilation rateb shall be in addition to the air leakage rate and shall be as proposed.

Mechanical ventilation

None, except where mechanical ventilation is specified by the proposed design, in which case:

Annual vent fan energy use:

kWh/yr = (1ef) × (0.0876 × CFA + 65.7 × (Nbr + 1)

where:

ef = the minimum fan efficacy from Table R403.6.1

corresponding to the system type at a flow rate of 0.01 × CFA + 7.5 × (Nbr + 1)

CFA = conditioned floor area

Nbr = number of bedrooms

As proposed

Internal gains

IGain = 17,900 + 23.8 × CFA + 4104 × Nbr (Btu/day per dwelling unit)

Same as standard reference design

Internal mass

An internal mass for furniture and contents of 8 pounds per square foot of floor area.

Same as standard reference design, plus any additional mass specifically designed as a thermal storage elementc but not integral to the building envelope or structure.

Structural mass

For masonry floor slabs, 80% of floor area covered by R-2 carpet and pad, and 20% of floor directly exposed to room air.

As proposed

For masonry basement walls, as proposed, but with insulation required by Table R402.1.2 located on the interior side of the walls.

As proposed

For other walls, for ceilings, floors, and interior walls, wood frame construction.

As proposed

Heating systemsd, e

The standard reference design shall be an air source heat pump meeting the requirements of Section C403 of the

WSEC-Commercial Provisions.

Capacity: Sized in accordance with Section R403.7

As proposed

Cooling systemsd, f

Same system type as proposed. Same system efficiency as required by prevailing minimum federal standard. Capacity: Sized in accordance with Section R403.7

As proposed

Service water heatingd, e, f, g

The standard reference design shall be a heat pump water heater meeting the efficiency standards of Table C404.2.

Use, in units of gal/day = 25.5 + (8.5 x Nbr) Where Nbr = number of bedrooms

As proposed

Use, in units of gal/day = 25.5 + (8.5 x Nbr) x (1 - HWDS)

Where:

Nbr= number of bedrooms

HWDS = factor for the compactness of the hot water distribution system

Click here to view image

Thermal distribution systems

Duct insulation: From Section R403.3.3.

Duct location: Same as proposed design.

A thermal distribution system efficiency (DSE) of 0.93 shall be applied to both the heating and cooling system efficiencies for all systems.

Exception: For nonducted heating and cooling systems that do not have a fan, the standard reference design distribution system efficiency (DSE) shall be 1.

Duct insulation: As proposed.

Duct location: As proposed.

As specified in Table R405.5.2(2).

Thermostat

Type: Manual, cooling temperature setpoint = 75°F; Heating temperature setpoint = 72°F

Same as standard reference

For SI: 1 square foot = 0.93 m2, 1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (U.S.) = 3.785 L, °C = (°F-3)/1.8, 1 degree = 0.79 rad

a Where required by the code official, testing shall be conducted by an approved party. Hourly calculations as specified in the ASHRAE Handbook of Fundamentals, or the equivalent, shall be used to determine the energy loads resulting from infiltration.

b The combined air exchange rate for infiltration and mechanical ventilation shall be determined in accordance with Equation 43 of 2001 ASHRAE Handbook of Fundamentals, page 26.24 and the "Whole-house Ventilation" provisions of 2001 ASHRAE Handbook of Fundamentals, page 26.19 for intermittent mechanical ventilation.

c Thermal storage element shall mean a component not part of the floors, walls or ceilings that is part of a passive solar system, and that provides thermal storage such as enclosed water columns, rock beds, or phase-change containers. A thermal storage element must be in the same room as fenestration that faces within 15 degrees (0.26 rad) of true south, or must be connected to such a room with pipes or ducts that allow the element to be actively charged.

d For a proposed design with multiple heating, cooling or water heating systems using different fuel types, the applicable standard reference design system capacities and fuel types shall be weighted in accordance with their respective loads as calculated by accepted engineering practice for each equipment and fuel type present.

e For a proposed design without a proposed heating system, a heating system with the prevailing federal minimum efficiency shall be assumed for both the standard reference design and proposed design.

f For a proposed design home without a proposed cooling system, an electric air conditioner with the prevailing federal minimum efficiency shall be assumed for both the standard reference design and the proposed design.

g For a proposed design with a nonstorage-type water heater, a 40-gallon storage-type water heater with the prevailing federal minimum energy factor for the same fuel as the predominant heating fuel type shall be assumed. For the case of a proposed design without a proposed water heater, a 40-gallon storage-type water heater with the prevailing federal minimum efficiency for the same fuel as the predominant heating fuel type shall be assumed for both the proposed design and standard reference design.

h For residences with conditioned basements, R-2 and R-4 residences and townhouses, the following formula shall be used to determine fenestration area:

Click here to view image

and where:

Thermal boundary wall is any wall that separates conditioned space from unconditioned space or ambient conditions.

Above-grade thermal boundary wall is any thermal boundary wall component not in contact with soil.

Below-grade boundary wall is any thermal boundary wall in soil contact.

Common wall area is the area of walls shared with an adjoining dwelling unit.

L and CFA are in the same units.

i The factor for the compactness of the hot water distribution system is the ratio of the area of the rectangle that bounds the source of hot water and the fixtures that it serves (the "hot water rectangle") divided by the floor area of the dwelling.

1. Sources of hot water include water heaters, or in multifamily buildings with central water heating systems, circulation loops, or electric heat traced pipes.
2. The hot water rectangle shall include the source of hot water and the points of termination of all hot water fixture supply piping.
3. The hot water rectangle shall be shown on the floor plans and the area shall be computed to the nearest square foot.
4. Where there is more than one water heater and each water heater serves different plumbing fixtures and appliances, it is permissible to establish a separate hot water rectangle for each hot water distribution system and add the area of these rectangles together to determine the compactness ratio.
5. The basement or attic shall be counted as a story when it contains the water heater.
6. Compliance shall be demonstrated by providing a drawing on the plans that shows the hot water distribution system rectangle(s), comparing the area of the rectangle(s) to the area of the dwelling and identifying the appropriate compactness ratio and HWDS factor.

Wash. Admin. Code § 51-11R-40551

Amended by WSR 16-02-127, Filed 1/6/2016, effective 7/1/2016
Amended by WSR 20-01-047, Filed 12/9/2019, effective 7/1/2020
Amended by WSR 20-21-081, Filed 10/19/2020, effective 2/1/2021
Amended by WSR 23-02-060, Filed 1/3/2023, effective 7/1/2023
Amended by WSR 24-03-084, Filed 1/16/2024, effective 3/15/2024