Table 1. 300 kW Capacity or Less.
Single-Phase | Three-Phase | |||
Feature | < 50 kW Inverter based | < 50 kW Noninverter based | < 300 kW Inverter based | < 300 kW Noninverter based |
IEEE 1547 compliant | X | X | X | X |
UL 1741 listed | X | X | ||
Interrupting devices (capable of interrupting maximum available fault current) | X (8) | X | X (8) | X |
Interconnection disconnect device (manual, lockable, visible, accessible) | X (1) | X | X | X |
System protection | X (3)(4)(6) | X (3)(4)(5)(6) | ||
Over-voltage trip | X (8) | X | X (8) | X |
Under-voltage trip | X (8) | X | X (8) | X |
Over/under frequency trip | X (8) | X | X (8) | X |
Automatic synchronizing check | X | X | ||
Ground over-voltage or over-current trip for utility system faults | X (2) | |||
Power factor | X (7) | X (7) |
Notes: | |
X - Required feature (blank = not required). | |
(1) - Electrical company may choose to waive this requirement. | |
(2) - May be required by electrical company; selection based on grounding system. | |
(3) - No single point of failure shall lead to loss of protection. | |
(4) - All protective devices shall fully meet the requirements of American National Standards Institute C37.90. | |
(5) - Electrical company will specify the transformer connection. | |
(6) - It is the customer's responsibility to ensure that its system is effectively grounded as defined by IEEE Std. 142 at the point of common coupling. | |
(7) - Variance may be allowed based upon specific requirements per electrical company review. Charges may be incurred for losses. | |
(8) - UL 1741 listed equipment provides required protection. |
Such waiver granted by the electrical company to the interconnection customer must be explicit and in writing.
Wash. Admin. Code § 480-108-020
Statutory Authority: RCW 80.01.040 and 80.04.160. WSR 07-20-059 (Docket UE-060649, General Order 545), § 480-108-020, filed 9/27/07, effective 10/28/07; WSR 06-07-017 (Docket No. UE-051106, General Order No. R-528), § 480-108-020, filed 3/6/06, effective 4/6/06.