(1) Dosing Chamber The dosing chamber, access riser and riser cover shall be watertight, structurally sound and not subject to excessive corrosion or decay. The dosing chamber shall be of one (1) compartment design. They shall be of such construction and size as specified in paragraphs (2), (3), and (4) of Rule0400-48-01-.09, excluding those requirements strictly relating to two (2) compartments.
(a) The access riser shall have a minimum diameter of twenty-four (24) inches and extend to the finished grade or above. Rectangular or square risers may be allowed provided the size of the opening provides the equivalent access as a circular riser. An access riser with a minimum diameter of sixteen (16) inches may be used provided the threaded union on the pump outlet pipe is located within two (2) feet of the top of the access riser. The access riser shall be located near the outlet end of the tank, directly above the pump or siphon, supply line, switches and other fixtures.(b) The dosing chamber volume shall be a minimum of two (2) times daily wastewater flow except when an alternate pump equipped with an in-tank supply line and switch assembly is on-site and ready for use. If the alternate pump, in-tank supply line and switch assembly is on-site and ready for use, the minimum dosing chamber volume shall be a total of the volume of water below the static level plus the designed dosing volume plus one-half (1/2) the daily flow.