New boilers without manholes shall have a minimum of three feet clearance from the top of the boiler to the boiler room ceiling. Replacement boilers located in the same boiler room shall comply as closely as possible.
S.D. Admin. R. 61:08:08:02
General Authority: SDCL 34-29A-16.
Law Implemented: SDCL 34-29A-24.