S.D. Admin. R. 20:10:39:44

Current through Register Vol. 50, page 159, June 17, 2024
Section 20:10:39:44 - Data collection for the secondary neutral voltage drop test

The following data is collected for each secondary neutral tested:

(1) Gauge and type of neutral wire;
(2) Length of neutral wire;
(3) Neutral current;
(4) Voltage drop between both ends of the secondary neutral being tested;
(5) Cow contact voltage or cow contact current at the same points used in the 48 hour test;
(6) Voltage from the primary neutral at the transformer to remote reference electrode; and
(7) Voltage from secondary neutral in the service panel serving the area of the cow contact to remote reference electrode.

S.D. Admin. R. 20:10:39:44

42 SDR 174, effective 6/21/2016

General Authority: SDCL 49-47-2.

Law Implemented: SDCL 49-47-2, 49-47-3.