S.C. Code Regs. § § 8-1221

Current through Register Vol. 48, 12, December 27, 2024
Section 8-1221 - IRC R408.3 Unvented Crawl Space

For unvented under-floor spaces, the following items shall be provided:

1. Exposed earth shall be covered with a continuous vapor retarder meeting ASTME 1745 Class A. Joints of the vapor retarder shall overlap by 6 inches (152 mm) and shall be sealed or taped. The edges of the vapor retarder shall extend not less than 6 inches (152 mm) up the stem wall and shall be attached and sealed to the stem wall or insulation.
2. One of the following is provided for the under-floor space:
2.1. Continuously operated mechanical exhaust ventilation at a rate equal to 1 cubic foot per minute (0.47 L/s) for each 50 square feet (4.7 m2) of crawl space floor area, including an air pathway to the common area (such as a duct or transfer grille), and perimeter walls insulated in accordance with Section N1102.2.11 of this code.
2.2. Conditioned air supply sized to deliver at a rate equal to 1 cubic foot per minute (0.47L/s) for each 50 square feet (4.7 m2) of under-floor area, including a return air pathway to the common area (such as a duct or transfer grille), and perimeter walls insulated in accordance with the S.C. Energy Codes.
2.3. Plenum in existing structures complying with Section M1601.5, if under-floor space is used as a plenum.
2.4. Dehumidification sized in accordance with the manufacturer's specifications.

S.C. Code Regs. § 8-1221

Added by State Register Volume 37, Issue No. 6, eff June 28, 2013; State Register Volume 40, Issue No. 06, eff. 6/24/2016; State Register Volume 41, Issue No. 05, eff. 5/26/2017; State Register Volume 43, Issue No. 05, eff. 5/24/2019; State Register Volume 44, Issue No. 06, eff. 6/26/2020; State Register Volume 46, Issue No. 05, eff. 5/27/2022.