Surface seal requirements for well casing set forth herein shall also apply when a pitless adapter or unit is installed in a well. The seal shall cover that interval occupied by the pitless case from the point of casing connection to land surface. A cement grout seal shall not be allowed within the pitless unit or pitless adaptor sealing interval. The pitless adapter or unit sealing interval shall be sealed with unhydrated bentonite as described in OAR 690-210-0330 and 690-210-0340. The pitless adapter or unit, including the cap or cover, pitless case and other attachments, shall be designed and constructed to be watertight to prevent the entrance of contaminants into the well from surface or near-surface sources. Pitless units shall be vented to the atmosphere. Refer to OAR 690-210-0210 if the pitless adaptor or unit is to be used in conjunction with PVC casing.
NOTE: Prior to installing pitless well adapters or units on public, community, municipal, or public utility water supply wells, contact the Department of Human Resources. (See references to Health Division regulation in Appendix 210-1).
Or. Admin. Code § 690-210-0270
To view attachments referenced in rule text, click here to view rule.
Statutory/Other Authority: ORS 536.090, ORS 537.505-537.795, ORS 536.027, ORS 536.900 & ORS 537.992
Statutes/Other Implemented: ORS 536.090, ORS 537.505-537.795, ORS 536.900 & ORS 537.992