Exceptions:
"Containment system."
"Containment vessel."
"Excess flow valve."
"Highly toxic."
"Ozone-gas generator."
"Physiological warning threshold level."
"Reduced flow valve."
"Toxic."
Exception: Liquids that do not generate highly toxic or toxic fumes, mists or vapors.
Exception: Liquids that do not generate highly toxic or toxic fumes, mists or vapors.
Exception: Cylinders not exceeding 20 cubic feet ( 0.566 m3) at normal temperature and pressure (NTP) are allowed within gas cabinets or fume hoods.
Exception: In classrooms of Group B occupancies, cylinders with a capacity not exceeding 20 cubic feet ( 0.566 m3) at NTP are allowed in gas cabinets or fume hoods.
Exceptions:
Exception: Pressure relief devices on outdoor tanks provided exclusively for relieving pressure due to fire exposure are not required to be vented to a treatment system provided that:
Exceptions:
Exceptions:
Table 6004.2.2.7.5
Rate of release for cylinders and portable tanks
Vessel type | Nonliquefied (minutes) | Liquefied (minutes) |
Containers | 5 | 30 |
Portable tanks | 40 | 240 |
Exception: A gas detection system is not required for toxic gases when the physiological warning threshold level for the gas is at a level below the accepted PEL for the gas.
Exception: Signal transmission to a constantly attended control station is not required where not more than one cylinder of highly toxic or toxic gas is stored.
Exception: Automatic shutdown is not required for reactors utilized for the production of highly toxic or toxic compressed gases where such reactors are:
Exception: Where the gas-detection sampling point initiating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold, the shutoff valve in the gas valve enclosure for the branch line located in the piping distribution manifold enclosure shall automatically close.
Exception: Compressed gases located in gas cabinets complying with paragraph (C)(8)(f)(5003.8.6) of rule 1301:7-7-50 of the Administrative Code and paragraph (D)(1)(b)(6004.1.2) of this rule and located 5 feet (1524 mm) or more from buildings and 25 feet (7620 mm) or more from an exit discharge.
Exception: An automatic sprinkler system is not required when:
Exceptions:
Exception: An ozone gas generator within an approved pressure vessel where located outside of buildings.
Cabinets shall be braced for seismic activity in accordance with the building code as listed in rule 1301:7-7-80 of the Administrative Code.
Cabinets shall be mechanically ventilated in accordance with the mechanical code as listed in rule 1301:7-7-80 of the Administrative Code with not less than six air changes per hour.
The average velocity of ventilation at makeup air openings with cabinet doors closed shall not be less than 200 feet per minute (1.02 m/s).
Ozone gas-generator rooms shall not be normally occupied, and such rooms shall be kept free of combustible and hazardous material storage. Room access doors shall display an approved sign stating: "OZONE GAS GENERATOR-HIGHLY TOXIC-OXIDIZER."
Exceptions:
Replaces: 1301:7-7-60
Ohio Admin. Code 1301:7-7-60
Five Year Review (FYR) Dates: 12/15/2022
Promulgated Under: 119.03
Statutory Authority: 3737.22, 3737.82, 3737.83
Rule Amplifies: 3737.22, 3737.82, 3737.83
Prior Effective Dates: 07/01/1979, 06/01/1985, 06/15/1992, 07/01/1993, 09/01/1995, 03/30/1998, 09/01/2005, 07/01/2007, 11/01/2011, 12/15/2017