Section 33-24-05-1104 - Installation requirements
1. The owner or operator must support and protect ancillary equipment against physical damage and excessive stress due to settlement, vibration, expansion, or contraction.
2. The owner or operator must provide the type and degree of corrosion protection recommended by an independent corrosion expert, based on the information provided under subsection 3 of section 33-24-05-1101, to ensure the integrity of the tank system during use of the tank system. An independent corrosion expert must supervise the installation of a corrosion protection system that is field fabricated to ensure proper installation.
3. The owner or operator must obtain, and keep at the facility, written statements by those persons required to certify the design of the tank system and to supervise the installation of the tank system as required in sections 33-24-05-1102, 33-24-05-1103, and subsections 1 and 2. The written statement must attest that the tank system was properly designed and installed and that the owner or operator made repairs under sections 33-24-05-1102 and 33-24-05-1103. These written statements must also include the certification statement as required in subsection 4 of section 33-24-06-03.

N.D. Admin Code 33-24-05-1104

Adopted by Administrative Rules Supplement 2016-359, January 2016, effective 1/1/2016.

General Authority: NDCC 23-20.3-03

Law Implemented: NDCC 23-20.3-03, 23-20.3-04, 23-20.3-05