N.Y. Comp. Codes R. & Regs. tit. 9 § 1506.7

Current through Register Vol. 46, No. 50, December 11, 2024
Section 1506.7 - Ventilation

Motor vehicle storage facilities in a multiple dwelling or upon the premises thereof shall be provided with natural or mechanical ventilation capable of preventing the accumulation of flammable gases or vapors. Where such facilities do not have natural ventilation they shall have mechanical ventilation providing not less than six complete changes of air per hour at all times during occupancy of the garage. Where such facilities are located above grade, every room or space therein shall be provided with openings to the outer air, having a combined area of not less than two per cent of the floor area; or such rooms or space shall have mechanical ventilation providing six air changes per hour.

N.Y. Comp. Codes R. & Regs. Tit. 9 § 1506.7