Current through Register Vol. 46, No. 50, December 11, 2024
Section 1503.6 - Fire department connection(a) New sprinkler systems having more than 36 sprinkler heads shall be equipped with approved fire department connections, and such connections shall be constructed of corrosion-resistive metal, located on a street front of the building or structure not less than 18 inches or more than 36 inches above grade; when located more than two feet above grade, such connections shall not project beyond the building face. Such connections shall be marked with raised letters not less than one inch in size, reading as follows: AUTO SPKR.(b) The number of fire department connections required shall be determined by the department.N.Y. Comp. Codes R. & Regs. Tit. 9 § 1503.6