N.M. Code R. § 20.2.14.203

Current through Register Vol. 35, No. 11, June 11, 2024
Section 20.2.14.203 - Emission Limitations-Existing Equipment Equal to or Greater Than 5000M BTU/HOUR

After December 31, 1982, The owner or operator of existing coal burning equipment having a rated heat capacity equal to or greater than 5000 million British Thermal Units per hour (higher heating value) shall not permit, cause, suffer, or allow:

A. Particulate matter emissions to the atmosphere in excess of 0.05 pounds per million British Thermal Units of heat input (higher heating value); or
B. Fine particulate matter emissions of less than two microns equivalent aerodynamic diameter to the atmosphere in excess of 0.04 pounds per million British Thermal Units of heat input (higher heating value) as determined pursuant to Procedure II for fine particulate sampling from stationary coal burning equipment set forth in 20.2.14.400 NMAC - 20.2.14.499 NMAC or an equivalent method approved by the Department.

N.M. Code R. § 20.2.14.203

11/30/95; 20.2.14.203 NMAC - Rn, 20 NMAC 2.14.203 10/31/02