N.H. Admin. Code § Env-Wq 708.04

Current through Register No. 50, December 12, 2024
Section Env-Wq 708.04 - Piping and Flow Distribution Devices
(a) Piping and channels throughout the WWTP shall be designed to carry the maximum design flows as follows:
(1) Gravity influent sewers shall not be surcharged during normal operating conditions;
(2) Bottom channel corners shall be filleted, with the elimination of pockets and corners where solids can accumulate;
(3) Suitable gates, stop logs, or plates shall be placed in channels to seal off unused sections that might accumulate solids;
(4) Non-corrodible materials shall be used for gates; and
(5) Channels that may not be used for considerable periods of time shall have valved drains.
(b) Flow distribution devices shall be designed to:
(1) Control organic, solids, and hydraulic loading to WWTP process units;
(2) Provide distribution to individual treatment units to ensure equal distribution among all units;
(3) Provide visible status indication for influent flow to each unit via weirs, sluice gates, slide gates, control valves, or other means;
(4) Provide positive scum and foam removal in all channels and distribution structures that have a trapped-free surface; and
(5) Not rely on effluent weirs and flow route symmetry for flow control.
(c) Underflow shear gates for balancing flows shall not be permitted.

N.H. Admin. Code § Env-Wq 708.04

(See Revision Note at chapter heading for Env-Wq 700) #8590, eff 3-25-06

Amended byVolume XXXIV Number 46, Filed November 13, 2014, Proposed by #10693, Effective 10/15/2014, Expires10/15/2024.