Nev. Admin. Code § 477.Sec. 3.3

Current through August 29, 2024
Section 477.Sec. 3.3 - NEW
1. The inspections required pursuant to subsection 1 of NRS 477.097, must be performed in accordance with the standards set forth in NFPA 92, as adopted by reference in NAC 477.281.
2. In addition to the requirements set forth in subsection 2 of NRS 477.097, the owner or operator of any building equipped with a smoke control system shall maintain and make available for inspection, upon the request of the State Fire Marshal, a person authorized by the State Fire Marshal or a governing body, any inspection and testing documentation created during the three most recent inspections of the smoke control system.
3. A technician performing an inspection pursuant to NRS 477.097 shall:
(a) Comply with the requirements of NRS 477.099;
(b) Hold a certification issued in accordance with paragraph (b) of subsection 1 of NRS 477.097; and
(c) In addition to the requirements set forth in subsection 2 of NRS 477.099, include in the certificate of inspection a description of any malfunctions or defects that were not fixed during the inspection of the smoke control system.
4. If the owner or operator of a building refuses a scheduled inspection, the technician must, not later than the end of the next business day after the date of the refusal, send a notice of refusal to the owner or operator of the building, the State Fire Marshal and the governing body.
5. As used in this section, "governing body" has the meaning ascribed to it in NRS 477.091.

Nev. Admin. Code § 477.Sec. 3.3

Added to NAC by St. Fire Marshal by R048-24A, eff. 8/26/2024

NRS 477.030, 477.097, 477.099