Section 459.9948 - Underground storage tanks: Under-dispenser container required for certain motor fuel dispensers1. Except as otherwise provided in subsection 3, under-dispenser containment is required for all new fuel dispenser systems that are installed on or after July 1, 2008, at a location where there was no previous dispenser or at a location to replace an existing dispenser and the equipment used to connect the dispenser to the underground storage tank is replaced.2. Under-dispenser containment must: (a) Meet the criteria prescribed in 40 C.F.R. § 280.20(f);(b) Be compatible with the substance conveyed by dispenser piping; and(c) At all times, be made available for inspection by the Division. 3. The Division may waive the requirements of this section if the owner or operator of a new fuel dispenser system demonstrates that the system is too large to be contained using a typical prefabricated containment sump, and the system is: (a) Located at an airport and used to fuel small aircraft; or(b) Part of a bulk fueling operation.Nev. Admin. Code § 459.9948
Added to NAC by Environmental Comm'n by R005-08, eff. 4-17-2008; A by R106-16A, eff. 11/2/2016