The owner or operator of a class II waste combustor must comply with:
The table in this subpart governs emission limitations for a class II waste combustor. For acid gas limitations, either the applicable percent reduction or the parts per million by volume emission limitation, whichever is less stringent, is the emission limitation for the waste combustor.
Size | Class II |
Particulate matter | |
Filterable | 0.015 gr/dscf |
The sum of filterable and organic condensable | 0.020 gr/dscf |
PCDD/PCDF | |
(total) | 30 ng/dscm |
Acid gases | |
HCl | 90% control or 25 ppm |
SO2 | 80% control or 30 ppm |
Carbon monoxide | |
Modular | 50 ppm |
Mass burn or fluidized bed | 100 ppm |
RDF stoker | 150 ppm |
Opacity | 10% |
NO x | NA |
Mercury (short-term) | |
Modular | 100 µg/dscm or 85% removal |
Mass Burn | 100 µg/dscm or 85% removal |
RDF (90-day test interval) | 50 µg/dscm or 85% removal |
FBC | 100 µg/dscm or 85% removal |
Mercury (long-term) | |
Modular | 60 µg/dscm or 85% removal |
Mass burn | 60 µg/dscm or 85% removal |
RDF (90-day test interval) | 30 µg/dscm or 85% removal |
FBC | 60 µg/dscm or 85% removal |
RDF (12-month test interval) | 30 µg/dscm or 85% removal |
Minn. R. agency 167, ch. 7011, WASTE COMBUSTORS, pt. 7011.1229
Statutory Authority: MS s 116.07