Minn. R. agency 144, ch. 4720, pt. 4720.3925

Current through Register Vol. 49, No. 29, 2025
Part 4720.3925 - SHORE WELLS

Shore well structures must:

A. have motors and electrical controls located above grade and flood level;
B. be accessible for operation and service;
C. be designed to prevent flotation;
D. be equipped with removable or traveling screens before the pump suction well;
E. provide chlorination or other chemical addition facilities for raw water transmission mains;
F. have the intake valved with provisions for backflushing and testing for leaks; and
G. have provisions for controlling surges.

Minn. R. agency 144, ch. 4720, pt. 4720.3925

15 SR 1842

Statutory Authority: MS s 144.383