Current through Register Vol. 49, No. 29, 2025
Intake structures must provide:
A. a velocity of flow 0.25 to 0.50 feet per second through the inlet structure so frazil ice is held to a minimum;B. for the withdrawal of water from the depth of the best water quality;C. inspection manholes every 1,000 feet for pipe sizes large enough to permit visual inspection;D. protection against rupture by dragging anchors, ice, and other activity; andE. permanent monuments to reference locations.Minn. R. agency 144, ch. 4720, pt. 4720.3922
Statutory Authority:MS s 144.383