Mich. Admin. Code R. 29.7060

Current through Vol. 24-24, January 15, 2025
Section R. 29.7060 - Sprinkler protection

Rule 60. Section 6-5 of the storage and handling of gaseous and Liquefied H2 code is added as follows:

6-5 When sprinkler protection is provided, the area in which H2 is stored or used shall be protected with an automatic sprinkler system designed to be not less than that required by NFPA 13, "standard for the installation of sprinkler systems," adopted by reference in section 8-1.

Mich. Admin. Code R. 29.7060

2008 AACS