Mich. Admin. Code R. 29.7059

Current through Vol. 24-24, January 15, 2025
Section R. 29.7059 - Fire protection

Rule 59. Section 6-4 of the storage and handling of gaseous and Liquefied H2 code is added as follows:

6-4 A portable fire extinguisher having a rating of not less than 40-B:C, or 2 20-B:C, shall be located within 75 feet (22.9 meters) from the pumps, dispensers, and container fill openings. Fire extinguishers shall be inspected and maintained according to NFPA 10, "standard for portable fire extinguishers," adopted by reference in section 8-1.1.

Mich. Admin. Code R. 29.7059

2008 AACS