Rule 719j.
Source Water Type | Populatio n size category | Monitorin g Frequency * | Distribution system monitoring location per monitoring period |
Subpart H | less than 500 | monitoring may not be reduced | |
Subpart H | 500 to 3,300 | per year | 1 TTHM and 1 HAA5 sample: 1 at the location and during the quarter with the highest TTHM single measurement, 1 at the location and during the quarter with the highest HAA5 single measurement; 1 dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter. |
Subpart H | 3,301 to 9,999 | per year | 2 dual sample sets: 1 at the location and during the quarter with the highest TTHM single measurement, 1 at the location and during the quarter with the highest HAA5 single measurement. |
Subpart H | 10,000 to 49,999 | per quarter | 2 dual sample sets at the locations with the highest TTHM and highest HAA5 LRAAs. |
Subpart H | 50,000 to 249,999 | per quarter | 4 dual sample sets--at the locations with the 2 highest TTHM and 2 highest HAA5 LRAAs. |
Subpart H | 250,000 to 999,999 | per quarter | 6 dual sample sets--at the locations with the 3 highest TTHM and 3 highest HAA5 LRAAs. |
Subpart H | 1,000,000 to 4,999,999 | per quarter | 8 dual sample sets--at the locations with the 4 highest TTHM and 4 highest HAA5 LRAAs. |
Subpart H | greater than or equal to 5,000,000 | per quarter | 10 dual sample sets--at the locations with the 5 highest TTHM and 5 highest HAA5 LRAAs. |
Groundw ater | less than 500 | every third year | 1 TTHM and 1 HAA5 sample: 1 at the location and during the quarter with the highest TTHM single measurement, 1 at the location and during the quarter with the highest HAA5 single measurement; 1 dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter. |
Groundw ater | 500 to 9,999 | per year | 1 TTHM and 1 HAA5 sample: 1 at the location and during the quarter with the highest TTHM single measurement, 1 at the location and during the quarter with the highest HAA5 single measurement; 1 dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter. |
Groundw ater | 10,000 to 99,999 | per year | 2 dual sample sets: 1 at the location and during the quarter with the highest TTHM single measurement, 1 at the location and during the quarter with the highest HAA5 single measurement. |
Groundw ater | 100,000 to 499,999 | per quarter | 2 dual sample sets; at the locations with the highest TTHM and highest HAA5 LRAAs. |
Groundw ater | greater than or equal to 500,000 | per quarter | 4 dual sample sets at the locations with the 2 highest TTHM and 2 highest HAA5 LRAAs. |
* Supplies on quarterly monitoring shall take dual sample sets every 90 days.
Mich. Admin. Code R. 325.10719j