Current through Register Vol. 51, No. 22, November 1, 2024
Section 09.17.02.07 - Automatic ShutdownA computerized monitoring system shall be equipped with an automatic burner shutdown mechanism that will activate when:
A. Stack flue gas reaches high temperature; andB. One of the following occurs, as applicable:(1) For a steam boiler: (a) Steam reaches high pressure; or(b) Water reaches Low or high level;(2) For a hot water boiler operating at 30 to 299 horsepower, water reaches high temperature; or(3) For a hot water boiler operating at 300 or more horsepower, water reaches: Md. Code Regs. 09.17.02.07