Section 09.17.02.06 - AlarmA computerized monitoring system shall be equipped with an alarm that will activate when:
A. The stack flue gas reaches a high temperature;B. The burner status indicator indicates the burner is "off";C. The flame safety control status indicates a "flame failure"; andD. One of the following occurs, as applicable:(1) For steam boilers, the: (a) Steam reaches low or high pressure; or(b) Water reaches low or high level;(2) For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or(3) For a hot water boiler operating at 300 or more horsepower the water reaches low or high: Md. Code Regs. 09.17.02.06