Section 09.17.02.06 - Alarm

A computerized monitoring system shall be equipped with an alarm that will activate when:

A. The stack flue gas reaches a high temperature;
B. The burner status indicator indicates the burner is "off";
C. The flame safety control status indicates a "flame failure"; and
D. One of the following occurs, as applicable:
(1) For steam boilers, the:
(a) Steam reaches low or high pressure; or
(b) Water reaches low or high level;
(2) For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or
(3) For a hot water boiler operating at 300 or more horsepower the water reaches low or high:
(a) Pressure;
(b) Temperature; or
(c) Level.