Section 28-19-713d - Compliance demonstration, monitoring, and reporting requirements

No later than 24 months after the effective date of this regulation, each owner or operator of any emission unit subject to the nitrogen oxide emission limits specified in K.A.R. 28-19-713a or K.A.R. 28-19-713b shall meet the following requirements:

(a) Demonstrate compliance with the applicable emissions limit by performing an emissions test in accordance with 40 C.F.R. 60.8, as adopted by reference in K.A.R. 28-19-720, and either of the following:
(1) Test method 7, 7A, 7C, 7D, or 7E in appendix A-4 to 40 C.F.R. part 60, as adopted by reference in K.A.R. 28-19-720 ; or
(2) any other USEPA test method approved by the department;
(b) ensure continuous compliance with the applicable emissions limit by installing, calibrating, maintaining, and operating a continuous emission monitoring system (CEMS) for nitrogen oxides that meets the requirements of 40 C.F.R. 60.13 and performance specification 2 in appendix B to 40 C.F.R. part 60, as adopted by reference in K.A.R. 28-19-720 ;
(c) certify the CEMS at least three months before the compliance demonstration required by subsection (a) pursuant to either of the following:
(1) The quality assurance procedures in appendix F to 40 C.F.R. part 60, as adopted by reference in K.A.R. 28-19-720 ; or
(2) an equivalent quality assurance procedure approved by the department; and
(d) document compliance by continuously monitoring and maintaining records of nitrogen oxide emissions.

Kan. Admin. Regs. § 28-19-713d

Authorized by K.S.A. 2009 Supp. 65-3005; implementing K.S.A. 65-3010; effective June 25, 2010.