675 Ind. Admin. Code 14-4.4-8

Current through December 12, 2024
Section 675 IAC 14-4.4-8 - Section R302.5.1; opening protection

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 8.

Change SECTION R302.5.1 to read as follows:

SECTION R302.5.1 OPENING PROTECTION.

Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and the residence shall be equipped with solid wood doors not less than 1 and 3/8 inches (35 mm) in thickness, solid or honeycomb-core steel doors not less than 1 and 3/8 inches (35 mm) thick, or 20 minute fire-rated doors. Pull down stairs that have a 20 minute fire rating may be installed in garage/attic separations.

675 IAC 14-4.4-8

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-8; field 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA