675 Ind. Admin. Code 14-4.4-79

Current through May 29, 2024
Section 675 IAC 14-4.4-79 - Section R703.8.6; drained cavity

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 79.

Delete SECTION R703.8.6 in its entirety and substitute to read as follows:

SECTION R703.8.6 DRAINED CAVITY.

The 3/4 inch (19 mm) air cavity shall be drained to the exterior of the structure at intervals of not more than 33 inches (838 mm) on center. Each drain shall be not less than 3/16 inch (4.8 mm) in diameter, located immediately above the flashing. For dwellings with crawlspaces, the air cavity may be drained as shown in FIGURE R703.8.6(1). For dwellings with basements, the air cavity may be drained as shown in FIGURE R703.8.6(2).

Click here to view Image

675 IAC 14-4.4-79

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-79; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA