Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7
Sec. 24.
Add SECTION R314.3.2 to read as follows:
SECTION R314.3.2 PROHIBITED SMOKE ALARM LOCATIONS.
A smoke alarm required under this section shall not be placed:
1. within 3 feet (914 mm) horizontally from any grille moving conditioned air within the living space, or a door or opening of a bathroom containing a bathtub or shower; or 2. in any location or environment prohibited by the terms of the listing.Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-24; field 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA