675 Ind. Admin. Code 14-4.4-213

Current through May 29, 2024
Section 675 IAC 14-4.4-213 - Section E3901.11; foyers

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 213.

Change the text of SECTION E3901.11 to read as follows:

Foyers that are not part of a hallway in accordance with Section E3901.10 and that have an area that is greater than one hundred (100) square feet (9.29 m2) shall have a receptacle located in each wall space that is 4 feet (1,219 mm) or more in width. The four (4) foot (1,219 mm) measurement shall be measured in a straight line. Doorways, door-side windows that extend to the floor, and similar openings shall not be considered as wall space. (210.52(H))

675 IAC 14-4.4-213

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-213; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA