675 Ind. Admin. Code 14-4.4-207

Current through May 29, 2024
Section 675 IAC 14-4.4-207 - Section E3702.12.2; where lighting units or other appliances are also supplied

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 207.

Change the text of SECTION E3702.12.2 to read as follows:

The total marked rating of a cord- and attachment plug-connected room air conditioner shall not exceed 50 percent of the rating of a branch circuit where lighting outlets, other appliances, or general use receptacles are also supplied. Where the circuitry is interlocked to prevent simultaneous operation of the room air conditioner and energization of other outlets on the same branch circuit, a cord- and attachment plug-connected room air conditioner shall not exceed 80 percent of the branch-circuit rating. (440.62(C))

675 IAC 14-4.4-207

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-207; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA