675 Ind. Admin. Code 14-4.4-134

Current through December 12, 2024
Section 675 IAC 14-4.4-134 - Section G2411.2.6; separation

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 134.

Add SECTION G2411.2.6 to read as follows: SECTION G2411.2.6 SEPARATION.

Except where connected to appliances and at bonding connections, corrugated stainless steel tubing that is not listed with an arc-resistant jacket or coating system in accordance with ANSI LC1/CSA 6.26 shall be isolated from metal gas piping, metal water piping, metal air ducts, metal structural framing, and all electrical wiring methods by a separation space of at least 2 inches.

675 IAC 14-4.4-134

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-134; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA