675 Ind. Admin. Code 14-4.4-116

Current through December 12, 2024
Section 675 IAC 14-4.4-116 - Section M1305.1.3.1; ground clearance

Authority: IC 22-13-2-2; IC 22-13-2-2.5; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 116.

Change the text of SECTION M1305.1.3.1 to read as follows:

Equipment and appliances supported from the ground shall be level and firmly supported on a concrete slab or other approved material not less than 2 inches (51 mm) above the finished grade. Such support shall be in accordance with the manufacturer's installation instructions. Appliances suspended from the floor shall have a clearance of not less than 6 inches (152 mm) from the ground.

675 IAC 14-4.4-116

Fire Prevention and Building Safety Commission; 675 IAC 14-4.4-116; filed 11/26/2019, 11:43 a.m.: 20191225-IR-675190330FRA