Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. F

Current through Register Vol. 48, No. 50, December 13, 2024
Table F - General Pressure Relationships and Ventilation of Certain Hospital Areas

Area Designation

Pressure Relationship To Adjacent Areas

Minimum Total Air Changes Per Hour Supplied To Room

All Air Exhausted Directly To Outdoors

Recirculation Within Room Units

Operating Room

+

12

Optional

No

Emergency Operating Room

+

12

Optional

No

Delivery Room

+

12

Optional

No

*Soiled Workroom or

*Soiled Holding Room

-

10

Yes

No

*Clean Workroom or

*Clean Holding Room

+

4

Optional

Optional

*Autopsy

-

10

Yes

No

*Toilet Room

-

10

Yes

No

*Bedpan Room

-

10

Yes

No

*Bathroom

-

10

Yes

No

*Janitors' Closet

-

10

Yes

No

*Sterilizer Equipment Room

-

10

Yes

No

*Food Preparation Centers

0

10

Yes

No

*Dietary Day Storage

0

2

Optional

No

*Laundry, General

0

10

Yes

No

*Soiled Linen Sorting and

*Storage Rooms

-

10

Yes

No

*Anesthesia Storage

0

8

Yes

No

Symbol Key: + = Positive - = Negative O= Equal * = Recommended

Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. F

Amended at 11 Ill. Reg. 10642, effective July 1, 1987