Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. E

Current through Register Vol. 48, No. 50, December 13, 2024
Table E - Piping Locations for Oxygen, Vacuum and Medical Compressed Air

Location

Oxygen

Vacuum

Compressed Air

Patient Room for Adult Medical/Surgical Care

A

A

Patient Room for Postpartum Care & Pediatrics

A

F

Examination and Treatment Rooms for Nursing Unit

D

D

Patient Room for Intensive Care

C

C

B

Normal Newborn Nursery

A

B

A

Special Care & Observation Nursery

B

B

A

General Operating Room

E

E

E

Cystoscopy and Special Procedure Room

D

D

D

Recovery Room for Surgical and Obstetrical Patients

B

B

A

Delivery Room

E

E

Labor Room

A

A

Treatment Room for Emergency Care

D

D

Autopsy Room

-

D

Anesthesia Workroom

-

D

A

=

One outlet accessible to each bed

One outlet may serve 2 beds

B

=

One outlet for each bed

C

=

Two outlets for each bed

D

=

One outlet

E

=

Two outlets

F

=

One outlet provided if required by the narrative

Ill. Admin. Code tit. 77, pt. 250, subpt. W, tbl. E