Haw. Code R. § 6-77-46

Current through April, 2024
Section 6-77-46 - Tapping
(a) Each mechanical fitting used to make a hot tap must be designed for at least the operating pressure of the pipeline.
(b) Where a ductile iron pipe is tapped, the extent of full-thread engagement and the need for the use of outside-sealing service connections, tapping saddles, or other fixtures must be determined by service conditions.
(c) Where a threaded tap is made in cast iron or ductile iron pipe, the diameter of the tapped hole may not be more than twenty-five percent of the nominal diameter of the pipe unless the pipe is reinforced, except that:
(1) Existing taps may be used for replacement service, if they are free of cracks and have good threads; and
(2) A 1-1/4-inch tap may be made in a four inch cast iron or ductile iron pipe, without reinforcement.

However, in areas where climate, soil, and service conditions may create unusual external stresses on cast iron pipe, unreinforced taps may be used only on six inch or larger pipe.

Haw. Code R. § 6-77-46

[Eff ] (Auth: HRS § 269-6) (Imp: 49 C.F.R. §192.151, OCT 1, 1990)