Strike Section 603.1 of the International Plumbing Code in its entirety and insert new Section 603.1 in the Plumbing Code in its place to read as follows:
Size of water service pipe. The water service pipe shall be sized to supply water to the structure in the quantities and at the pressures required in this code. The water service pipe shall be not less than 1 inch (25.4 mm) in diameter.
Insert new Sections 603.3 through 603.3.3 and Table 603.3.1 to the Plumbing Code to read as follows:
Water service piping protection. Water service piping shall be protected against backflow in accordance with Sections 603.3.1 through 603.3.3. This section shall not apply to one and two-family dwellings.
Water service piping backflow prevention. A backflow prevention device shall be installed on the water service pipe, downstream of the water meter, in compliance with Table 603.3.1, for every new water service, and for existing water services as required by Section 603.3.3. Backflow prevention devices shall be installed in accordance with manufacturer's installation instructions and shall be located upstream from any served water outlet.
High Risk Non-Residential Structure. Any building, structure or campus that is or contains a facility hereafter classified as a high risk non-residential structure shall be required to install a reduced pressure principle backflow prevention assembly conforming to ASSE 1013 on the water service connection. High risk non-residential structures include, but are not limited to, hospitals, hemoglobin dialysis centers, funeral homes or mortuary facilities, chemical manufacturing plants, car wash facilities, sewage treatment plants, auxiliary water supply systems, wells, dry cleaning plants, laboratories, facilities where radioactive materials are handled, and facilities with a water reuse system.
Table 603.3.1 Water Service Backflow Prevention
Domestic Backflow Prevention Device
Facility type | Service Size | Type | Location Note a |
Residential or non-residential | 1", 1 1/2" and 2" | Dual Check Valve Type (ASSE 1024- compliant) | On the discharge side of meter yoke Note b |
Non-residential | 3" and larger | Double Check BFP Assembly (ASSE 1015-compliant) | Inside facility, within 10 feet of water service point of entry |
High Risk Non-residential | Any | Reduced Pressure Principle BF Preventer (ASSE 1013-compliant) |
Fire Protection Backflow Prevention Device
Water Treatment | Type | Location Note a |
No chemical additives | Double Check Fire Protection BFP Assembly (ASSE 1015 -compliant) Double Check Detector Fire Protection BFP Assembly (ASSE 1048 -compliant) | Inside facility, within 10 feet of water service point of entry |
Treated with chemical additives | Reduced Pressure Principle Fire Protection BF Preventer (ASSE 1013-compliant) Reduced Pressure Detector Fire Protection BFP Assembly (ASSE 1047-compliant) |
For SI: 1 inch = 25.4 mm, 1 ft = 304.8 mm, 1 pound per square inch = 6.895 kPa.
D.C. Mun. Regs. tit. 12, r. 12-F603