1 Del. Admin. Code § 706-3-3.0

Current through Register Vol. 28, No. 5, November 1, 2024
Section 706-3-3.0 - Fire Protection Systems Required in New Apartment Buildings
3.1Fire Alarm Signaling Systems. All new apartment buildings shall be provided with a fire alarm signaling system in accordance with the Life Safety Code, NFPA 101, as adopted and/or modified by these Regulations. Exception: Where each dwelling unit is separated from other contiguous dwelling units by fire barriers having a fire resistance rating of not less than one hour, and where each dwelling unit has either its own independent exit or its own independent stairway or ramp discharging at grade.
Note: This requirement also appears in Regulation 701 and reappears in this specific occupancy Chapter for clarification.
3.2 Local Fire Alarm Signaling Systems.
3.2.1 Where there is a local fire alarm system with pull stations, a sign shall be provided for each pull station. The sign shall read as follows:

LOCAL FIRE ALARM ONLY

In Case of Fire

1. Activate Pull Station
2. Dial 911 for Fire Department Response or similar wording acceptable to the State Fire Marshal.
3.2.2 The minimum size for each sign shall be three inches high by five inches wide (3"x5").
Note: The sign should be of durable construction and affixed firmly in the immediate vicinity of each pull station. The line of lettering should be a minimum of one half inch (1/2") high and use a plain font that is easy to read.
3.3 Buildings with less than 12 individual living units are not required to provide off-site monitoring by the fire alarm signaling system for the approved, automatic sprinkler system.
Note: This requirement also appears in Regulation 701 and reappears in this specific occupancy Chapter for clarification.

1 Del. Admin. Code § 706-3-3.0

19 DE Reg. 843 (3/1/2016) (Final)