780 CMR, ch. 51, ch. 3, R301, 301.1, 314.8

Current through Register 1538, January 3, 2025
Subsection 314.8

Add section R314.8 Heat detector as follows:

R314.8Heat detector. A single heat detector listed for the ambient environment shall be installed in:
1. Any garage attached to or under the dwelling (detached garages do not require a heat detector).
2. A new garage attached to an existing dwelling. If the existing dwelling contains a fire detection system that is compatible with the garage heat detector, then the detector shall be interconnected to that system. Where the existing fire detection system is not compatible with the garage heat detector, the garage heat detector shall be connected to an alarm (audible occupant notification), or compatible heat detector with an alarm, located in the dwelling and within 20 feet (6096 mm) of the nearest door to the garage from the dwelling. An alarm is not required in the garage, either integral with or separate from the heat detector.

Add section R314.8.1 Heat Detector Placement as follows:

R314.8.1Heat Detector Placement. For flat-finished ceilings, the heat detector shall be placed on or near the center of the garage ceiling. For sloped ceilings having a rise to run of greater than one foot in eight feet (305 mm in 2438 mm), the heat detector shall be placed in the approximate center of the vaulted ceiling but no closer than 4 inches (102 mm) to any wall. Heat detection shall be listed in accordance with UL 521 or UL 539.

780 CMR, ch. 51, ch. 3, R301, 301.1, 314.8

Amended by Mass Register Issue 1532, eff. 10/11/2024.