49 C.F.R. § 192.509

Current through May 31, 2024
Section 192.509 - Test requirements for pipelines to operate below 100 p.s.i. (689 kPa) gage

Except for service lines and plastic pipelines, each segment of a pipeline that is to be operated below 100 p.s.i. (689 kPa) gage must be leak tested in accordance with the following:

(a) The test procedure used must ensure discovery of all potentially hazardous leaks in the segment being tested.
(b) Each main that is to be operated at less than 1 p.s.i. (6.9 kPa) gage must be tested to at least 10 p.s.i. (69 kPa) gage and each main to be operated at or above 1 p.s.i. (6.9 kPa) gage must be tested to at least 90 p.s.i. (621 kPa) gage.

49 C.F.R. §192.509

35 FR 13257, 8/19/1970, as amended by Amdt. 192-58, 53 FR 1635, 1/21/1988; Amdt. 192-85, 63 FR 37504, 7/13/1998