49 C.F.R. § 192.373

Current through May 31, 2024
Section 192.373 - Service lines: Cast iron and ductile iron
(a) Cast or ductile iron pipe less than 6 inches (152 millimeters) in diameter may not be installed for service lines.
(b) If cast iron pipe or ductile iron pipe is installed for use as a service line, the part of the service line which extends through the building wall must be of steel pipe.
(c) A cast iron or ductile iron service line may not be installed in unstable soil or under a building.

49 C.F.R. §192.373

35 FR 13257, 8/19/1970, as amended by Amdt. 192-85, 63 FR 37503, 7/13/1998