49 C.F.R. § 192.359

Current through May 31, 2024
Section 192.359 - Customer meter installations: Operating pressure
(a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure.
(b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage.
(c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing.

49 C.F.R. §192.359

35 FR 13257, 8/19/1970, as amended by Amdt. 192-1, 35 FR 17660, 11/17/1970; Amdt. 192-85, 63 FR 37503, 7/13/1998